High Precision SF6 purity analyzer Sf6 Gas Purity Test Set
- Wrindu
- Shanghai, China
- about 25 days
- 5000 set/month
- RDCD-706
The SF6 Gas purity tester is based on reliable and high-quality imported SF6 purity sensors and is equipped with mass flow sensors, environmental humidity sensors and temperature sensors. It also uses the most popular and advanced embedded ARM technology to make sample data More real and more reliable. SF6 gas purity tester is mainly used to measure the SF6 gas purity of air, SF6, nitrogen mixed gas.
Description
The SF6 Gas purity tester is based on reliable and high-quality imported SF6 purity sensors and is equipped with mass flow sensors, environmental humidity sensors and temperature sensors. It also uses the most popular and advanced embedded ARM technology to make sample data More real and more reliable. SF6 gas purity tester is mainly used to measure the SF6 gas purity of air, SF6, nitrogen mixed gas. It can also exist in applications where multiple background gases exist (special requirements are required). The instrument uses a liquid crystal display screen, the interface is friendly and beautiful, easy to operate.
Features
1. Long life detection components
2. High accuracy and good repeatability
3. Built-in pressure regulator and electronic mass flow meter
4. Lightweight, portable and easy to use
5. Fast response, almost no warm-up waiting. The measurement result is not affected by the ambient temperature
For more SF6 gas testing equipment, please click SF6 gas testing solution
If your company has purchasing needs, please click to contact us, we are always ready to provide you with quotes and solutions.
Specifications
1. Range: 0 ~ 99.9% SF6;
2. Accuracy and repeatability: typical value ± 0.2% (within a certain length), regardless of flow rate;
3. Resolution: SF6 0.1%;
4. Response time: 60% (90%), 20s (45s);
5. Sampling: Built-in regulating valve, filter, flow meter; 5 meter sampling tube and one pressure reducing valve connector.
6. Working temperature: -30 ℃ to 50 ℃ (best accuracy);
7. Power supply: Lithium battery, AC and DC dual-use, automatic switching, overcharge and over discharge protection function
8. Sampling flow rate: 0.2L / min;
9. Weight about 3.4 kg, volume 358 × 240 × 108 (mm)