How to quickly detect SF6 purity on site to ensure normal operation of circuit breakers

07-11-2024


In the daily maintenance of electrical systems, SF6 purity testing is a critical task to ensure the proper functioning of circuit breakers. As SF6 gas is not only an efficient insulating medium but also provides excellent arc-quenching properties, maintaining its purity is vital. Below are the methods and steps for efficiently testing SF6 purity in the field, along with practical details.


sf6 gas purity tester

Using Portable SF6 Gas Analyzers for Testing


Why Choose Portable Analyzers?

Portable SF6 gas analyzers are widely used because they provide fast and reliable field analysis. These analyzers offer the following advantages:

  • Fast results in 5-10 minutes, minimizing downtime and operational interruptions.

  • Multiple parameter measurements, including purity, moisture content, and decomposition products, all in a single test.

  • Compact design and ease of use, making them ideal for outdoor and substation environments.


Operational Process

  • Connection and Sealing: Connect the sampling hose of the analyzer to the circuit breaker’s gas chamber. Ensure that the connection is sealed properly to avoid SF6 gas leakage.

  • Startup and Calibration: Before starting the test, check whether the equipment is properly calibrated. This step is crucial, especially after prolonged use or under extreme temperatures.

  • Sampling and Analysis: Start the analyzer and wait for 5-10 minutes. During this time, the device will measure the purity, moisture, and decomposition products (such as SO₂) in the SF6 gas.

  • Data Interpretation: Once the analysis is complete, review the results and interpret the parameters. Advanced models will automatically compare the readings to international standards (e.g., IEC 60376), providing clear indications of whether the gas is within acceptable limits.


Key Parameters for Interpretation

  • SF6 Purity: Typically, the acceptable range is above 98%. A value below this indicates possible contamination or leakage issues.

  • Moisture Content: Measured in terms of dew point or ppm, moisture should generally be below a dew point of -30°C. Excess moisture can create conductive paths under high voltage, compromising insulation.

  • Decomposition Products: High levels of sulfur dioxide (SO₂) indicate that the SF6 gas has decomposed and the circuit breaker may require maintenance.


Other Supporting Methods


Speed of Sound Method

The speed of sound method measures the velocity at which sound propagates through the SF6 gas to assess its purity. This method is highly accurate and useful for experienced engineers, though it may require additional calibration equipment.


Density and Pressure Measurement

By measuring the density and pressure of the SF6 gas, you can indirectly assess its purity. This method is most effective when combined with temperature compensation and is suitable for routine monitoring, though it has limitations in terms of precision.


Maintenance and Field Operation Best Practices


  • Routine Leak Checks: Use portable leak detectors to check for small gas leaks, particularly around joints and seals. Undetected leaks can gradually reduce SF6 purity.

  • Maintaining Stable Gas Pressure: After installation or maintenance, check the pressure gauge readings to ensure the gas pressure is within the recommended range. Pressure fluctuations can affect gas density, which in turn influences the insulation and arc-quenching capabilities.

  • Use Professional Gas Filling Equipment: When refilling SF6, ensure that certified filling and recovery equipment is used to prevent contamination or overfilling, both of which can lead to potential issues.

Case Example

During a routine inspection, a field technician used a portable SF6 gas analyzer to find that the SF6 concentration in a main transformer circuit breaker had dropped to 96%, with high moisture content. By quickly locating the leak source—at a seal interface—the technician was able to perform repairs and bring the SF6 concentration back up to 99%. This timely detection and repair helped avoid potential insulation failure. This case highlights the importance of fast and accurate field testing.

By following these steps and best practices, engineers can effectively ensure the reliable operation of circuit breakers, reduce maintenance costs, and comply with environmental regulations and safety standards.

RDCDF-706  SF6 Gas Purity Tester

sf6 gas purity tester



²  Product features

1.    5.0" TFT touch screen design

2.      32-bit ARM MCU

3.      Separately designed air way and circuit

4.      Large capacity storage function

5.      Digital display of battery electric quantity

6.      Good repeatability, high response speed

7.      Automatic calibration of gradient

8.      Color LCD display

9.      Advanced probe protection function

10.   Anti-pollution, anti-disturbance

11.   High sensitivity, good stability

12.   Small, beautiful, easy to carry