Intelligent Protection Relay Test Device
- Wrindu
- RDJB-1600M
Microcomputer Relay Protection Tester is a compact yet highly accurate solution developed with extensive user feedback. This tester offers superior performance, ease of use, and reliability at an unmatched price point, making it the perfect tool for relay protection professionals.
Description
Our RDJB-1600M Microcomputer Relay Protection Tester is the result of meticulous user feedback analysis and extensive market research on current domestic products. Utilizing cutting-edge microelectronic technology, we've developed a compact, high-accuracy testing solution. This device combines the superior performance and advanced features of large-scale testers with the compactness, flexibility, ease of use, and high reliability typically found in smaller models. Offering an exceptional performance-to-price ratio, it's the go-to tool for relay protection professionals.
Features
1. Versatile Output Options:
Our device offers flexible combinations of voltage and current output, supporting various testing configurations such as conventional four-phase current, three-phase current, six-phase voltage, six-phase current, and 12-phase output modes. This versatility allows compatibility with traditional testing methods and convenient differential testing of three-phase transformers.
2. Convenient Operation:
The device can operate independently or be controlled via an external laptop or desktop computer, ensuring efficient and stable performance.
3.High-Fidelity Linear Power Amplifier:
Featuring a new hi-fi linear power amplifier, our device prioritizes high fidelity and reliability over switching power amplifiers. This ensures minimal distortion, excellent waveform accuracy, and disturbance-free testing across a wide range of frequencies.
4. High-Performance Mainframe:
Equipped with DSP control, the output section delivers fast operation, real-time digital signal processing, and high-resolution D/A conversion control. Precision components, advanced technology, and professional design result in a compact, lightweight device with full functionality, easy portability, and convenient operation.
5. Comprehensive Software Functionality:
Our powerful software enables automatic validation of complex tasks, protection setting testing, fault playback, real-time data storage, vector display, and online report printing. Additionally, six-phase current support simplifies testing for three-phase differential protection.
6. Independent DC Power Output:
Designed with an adjustable 110V and 220V DC power output for added convenience.
7. Complete Interface:
Featuring a USB communication port for seamless connectivity with computers and other external devices.
8. Robust Self-Protection Features:
With a well-designed heat dissipation structure and reliable hardware protection measures, the device includes power soft start functionality, self-diagnostic software for fault detection, and an output latch function for enhanced safety and reliability.
Parameters
1. AC current source
The virtual value of each phase output when six phase current output: 0 ~ 30A; output precision: 0.2 grade
The virtual value of each phase output when three phase current output: 0 ~ 60A
The virtual value of six phase parallel current output: 0 ~ 180A
The allowed virtual value when the phase current work long time: 10A
The maximum output power of phase current: 300VA
The maximum output power when six phase parallel current output: 1000VA
The allowed working time when six phase parallel current maximum output: 5s
Frequency range (fundamental wave): 0 ~ 1000Hz
Harmonic order: 2 ~ 20
Phase: 0~360º
2. DC current source:
Current output: 0 ~ ±10A / phase ; output precision: 0.5 grade
The maximum load volatage output: 20V
3. AC voltage source:
The virtual value of phase voltage output: 0 ~ 120V output precision: 0.2 grade
The virtual value of line voltage output: 0 ~ 240V
The output power of phase voltage/ line voltage: 75VA / 100VA
Frequency range (fundamental wave): 0 ~ 1000Hz
Harmonic order: 2 ~ 20
Phase: 0~360º
4. DC voltage source
The output amplitude of phase voltage: 0 ~ ±160V ; output precision: 0.5 grade
The output amplitude of line voltage: 0 ~ ±320V
The output power of phase voltage/ line voltage: 70VA / 140VA
5. Switching terminal
8 channels input
Free contact: 1~20mA, 24V
Electric potential contacts: “0”:0 ~ +6V; “1”:+11V ~ +250V
4 channels output: 110V/2A; 220V/1A
6. Time measurement range:
1ms ~ 9999s , measurement accuracy 1ms
7. Power: AC220V ± 10% ; 50Hz